Misinterpreting a P&ID symbol can create serious safety risks. Incorrect valve choices may compromise tank integrity, leading to equipment damage, environmental incidents, and potential harm to personnel.
A breather valve P&ID symbol represents a pressure vacuum relief valve (PVRV). It typically combines two triangles: one pointing away from the process line to show pressure relief and one pointing towards it to show vacuum relief, indicating its dual function.

Correctly identifying this symbol on a Piping and Instrumentation Diagram (P&ID) is the first step in ensuring your storage tanks are properly protected from overpressure and vacuum. This guide will help you decode the symbol, understand its variations, and appreciate its role in overall system safety.
Decoding the Standard Breather Valve P&ID Symbol
In complex projects, inconsistent P&ID legends can cause confusion. Knowing the standard representation of a breather valve is essential for accurate engineering review and equipment specification.
The most common breather valve P&ID symbol consists of a valve body connected to a process line, often a tank nozzle, with both a pressure and a vacuum relief function shown. This dual-functionality is what distinguishes it from simple pressure relief valves.
Diving deeper, the symbol is based on principles outlined in standards like ISA-5.1, “Instrumentation Symbols and Identification.” While this standard provides a framework, many companies develop their own specific legends. Always refer to your project’s P&ID legend sheet for the definitive representation. The key is to identify the two core actions:
- Pressure Relief: This is typically shown with a symbol, like a triangle, indicating flow moving away from the tank or process line. When the internal pressure exceeds the valve’s setpoint, it opens to vent excess vapor to the atmosphere or a closed system.
- Vacuum Relief: This is represented by a symbol indicating flow moving into the tank. When pumping out liquid or during thermal in-breathing, the internal pressure drops. The valve opens to draw in air, equalizing the pressure and preventing the tank from collapsing.
These two functions are housed in a single valve body. The symbol on the P&ID will have a unique tag number (e.g., PV-101). This tag number is your link to the instrument data sheet, which contains all critical specifications: set pressure, set vacuum, flow capacity, body material, and flange rating. Without understanding the symbol, you cannot access this vital information.
Symbol Components Comparison
The table below shows how a breather valve symbol compares to pressure-only and vacuum-only relief devices.
| Device Type | Symbolic Representation | Primary Function |
|---|---|---|
| Pressure Relief Valve (PRV) | Shows flow moving OUT of the process line only. | Protects against overpressure. |
| Vacuum Relief Valve (VRV) | Shows flow moving INTO the process line only. | Protects against vacuum collapse. |
| Breather Valve (PVRV) | Shows flow moving BOTH out of and into the process line. | Provides both overpressure and vacuum protection. |
Understanding Variations of Breather Valve Symbols
A basic symbol shows the valve’s core function. However, P&IDs often include extra details to represent accessories or specific configurations like flame arresters or pipe-away designs.
Symbols become more specific to show integrated safety features or venting arrangements. These additions are critical for engineers to confirm that the selected valve matches the process requirements for safety and environmental compliance.
These variations provide a more complete picture of the tank’s protection system. As an engineer, recognizing them helps you verify that the design meets all safety and operational goals. For example, a symbol showing a pipe-away configuration immediately tells you that vapors are being managed, not freely vented.
Symbol for Breather Valve with Flame Arrester
When a breather valve is used on a tank storing flammable liquids, it is often equipped with a flame arrester. This essential safety device prevents an external flame from traveling back into the tank’s vapor space. On a P&ID, this is typically shown by adding the flame arrester symbol—often a box with a zig-zag or mesh pattern inside—to the inlet or outlet of the breather valve symbol. This visual cue is a critical checkpoint during safety reviews like a HAZOP analysis. It confirms that a key safeguard against fire and explosion is included in the design.

Symbol for Pipe-Away or In-line Models
Standard breather valves vent directly to the atmosphere. However, environmental regulations or process requirements may demand that vapors be collected. In these cases, a “pipe-away” breather valve is used. The P&ID symbol will show the valve’s outlet connected to a pipeline instead of venting open. This pipeline might lead to a vapor recovery unit, a scrubber, or a flare system. This detail on the diagram is crucial for confirming compliance with environmental standards and ensuring hazardous vapors are handled safely.
The Role of P&ID Symbols in Tank Protection System Design
The breather valve p&id symbol is not just a drawing. It is a fundamental part of the engineering language that defines your tank’s safety and operational boundaries.
This symbol helps engineers verify the correct placement and specification of the valve. It ensures the entire tank breathing system complies with design standards like API 2000 for venting atmospheric and low-pressure storage tanks.

During my early years in the valve industry, I worked on a project where a junior engineer had specified a simple pressure relief valve for a large diesel storage tank. The P&ID symbol only showed overpressure protection. During our review, we questioned the lack of vacuum protection. The tank was at risk of collapsing during rapid pump-out operations. By correcting the P&ID and specifying a proper breather valve, we prevented a costly and dangerous mistake. This experience taught me how crucial a simple symbol is for overall plant safety.
The P&ID serves as the master document for system design and safety analysis. The breather valve symbol on it confirms several key points:
- Correct Location: The symbol shows the valve is installed on a nozzle at the highest point of the tank, ensuring it operates in the vapor space.
- System Integration: The diagram illustrates how the breather valve works with other instruments, such as pressure transmitters, level gauges, and emergency vents, to form a complete protection layer.
- Foundation for HAZOP: During a Hazard and Operability (HAZOP) study, the team scrutinizes the P&ID. The breather valve symbol represents a critical safeguard against overpressure or vacuum scenarios. Its presence and correct specification are heavily questioned.
- Lifecycle Documentation: The tag number associated with the symbol is the start of a long documentation trail. It links the P&ID to the instrument index, the valve data sheet, procurement records, and future maintenance history. This traceability is essential for safe and efficient plant management.
Frequently Asked Questions (FAQ)
Q1: What is the primary function of a breather valve?
A: A breather valve, or pressure vacuum relief valve (PVRV), protects a storage tank from damage. It automatically vents excess pressure during filling or due to temperature changes (out-breathing) and allows air in to relieve vacuum during emptying or temperature drops (in-breathing).
Q2: How do you read a breather valve P&ID symbol?
A: Look for a valve symbol on a tank nozzle that indicates two-way flow. A symbol for pressure relief (flow out) and a symbol for vacuum relief (flow in) are combined. The exact drawing can vary, so always check your project’s P&ID legend for certainty.
Q3: Where can I find the official breather valve P&ID symbol standard?
A: The ISA-5.1 standard provides guidelines for instrumentation symbols, including those for relief valves. However, it is not a strict rule. Most engineering companies have their own detailed P&ID symbol libraries, which should be your primary reference on any given project.
Q4: What happens if you use the wrong breather valve on a tank?
A: Using the wrong valve can have severe consequences. If there is no vacuum relief, the tank could collapse during pump-out. If the pressure relief capacity is too low, the tank could rupture from overpressure. Correct selection based on API 2000 is critical for safety.
Q5: Does the P&ID symbol for a breather valve change based on its material?
A: No, the symbol itself does not typically change based on the valve’s material of construction (e.g., carbon steel, stainless steel, or fiberglass). Material specifications are detailed in the valve’s data sheet, which is linked to the symbol via its tag number.
Q6: How does a flame arrester change the breather valve symbol?
A: When a flame arrester is integrated with a breather valve, an additional symbol is added. This is often a box containing a zig-zag or mesh pattern, attached to the valve symbol. This indicates an added layer of protection against external ignition sources for flammable liquids.
Final Thought
The breather valve P&ID symbol is a vital communication tool for engineers, ensuring every tank is protected from the dangers of overpressure and vacuum. Always use your project’s P&ID legend as the final source of truth to avoid misinterpretation.
If you need help selecting the right, fully-compliant breather valve for your tank farm or processing plant, contact our team at BCST. We provide expert guidance to ensure your facility operates safely and reliably.