Protecting your storage tanks from overpressure or vacuum is critical. Incorrect pressure can lead to tank deformation or catastrophic failure, posing serious safety and financial risks.
A proper breather valve calculation is key to tank safety. It involves determining the required venting flow rates for both thermal effects and liquid movement, based on standards like API 2000, to select the correct valve size for your specific application.

Understanding the details of this calculation is not just a technical exercise; it’s a fundamental step in ensuring the integrity and safety of your entire facility. This guide will walk you through the process, helping you protect your valuable assets and personnel.
Understanding the Basics of Breather Valve Calculation
The primary goal of a breather valve calculation is to ensure your storage tank is never exposed to pressures or vacuums beyond its design limits.
This calculation quantifies the maximum required air flow in or out of the tank. This allows you to choose a pressure vacuum relief valve (PVRV), also known as a breather valve, that can handle these flows, preventing structural damage from overpressure or collapse from vacuum.
A breather valve is an automatic safety device designed to protect low-pressure storage tanks. Tanks are typically designed to withstand only small amounts of internal pressure or vacuum. When conditions change, pressure inside the tank can build up or drop significantly.
Two main phenomena drive these pressure changes:
- Outbreathing (Overpressure): This happens when the pressure inside the tank exceeds the set pressure of the valve. The valve opens to vent excess vapor to the atmosphere, preventing the tank from rupturing. This is caused by rising ambient temperatures or by filling the tank with liquid.
- Inbreathing (Vacuum): This occurs when the pressure inside the tank drops below the valve’s vacuum setting. The valve opens to allow air to enter, equalizing the pressure and preventing the tank from collapsing. This is caused by falling ambient temperatures or by emptying liquid from the tank.
The entire process of sizing and selection is governed by industry standards, with API Standard 2000, “Venting Atmospheric and Low-pressure Storage Tanks,” being the most widely recognized authority. A correct breather valve calculation translates these theoretical risks into a tangible, reliable piece of safety equipment.
Key Factors in Sizing: Inbreathing and Outbreathing
An accurate breather valve calculation depends on separately determining the maximum flow rates required for both inbreathing (vacuum relief) and outbreathing (pressure relief).
Outbreathing is caused by thermal expansion from daytime heating and vapor displacement during tank filling. Inbreathing results from thermal contraction during nighttime cooling and the vacuum created when emptying the tank. The calculation must account for the worst-case scenario for each condition.

Calculating Outbreathing (Pressure Relief) Requirements
Outbreathing is the process of venting vapors out of the tank to relieve pressure. The total outbreathing requirement is the sum of venting needs from thermal effects and tank filling.
Thermal Outbreathing: As the sun heats the tank during the day, the vapor inside expands, and more of the stored liquid evaporates. This increases the internal pressure. API 2000 provides tables that specify the required venting flow rate in Standard Cubic Feet per Hour (SCFH) or Normal Cubic Meters per Hour (Nm³/h) based on the tank’s volume. This simplifies the calculation for thermal effects.
Operational Outbreathing (Pumping In): When you fill a tank with liquid, the liquid displaces the vapor in the ullage (the space above the liquid). This vapor must be vented to prevent pressure buildup. The required venting rate is directly proportional to the maximum rate at which you pump liquid into the tank.
The total outbreathing requirement is typically the sum of these two rates, as a tank could be filled on a hot day.
Calculating Inbreathing (Vacuum Relief) Requirements
Inbreathing is the process of drawing air into the tank to relieve a vacuum. The total inbreathing requirement is the sum of venting needs from thermal effects and tank emptying.
Thermal Inbreathing: As the ambient temperature drops at night, the vapor inside the tank cools and contracts. Some of it may also condense back into liquid. This creates a vacuum. Similar to thermal outbreathing, API 2000 provides standard venting requirements based on tank capacity to counteract this effect.
Operational Inbreathing (Pumping Out): When you empty a tank, a vacuum is created as the liquid level drops. To prevent the tank from collapsing under atmospheric pressure, air must be allowed to enter and fill this space. The required inbreathing rate is equal to the maximum liquid withdrawal rate.
The total inbreathing requirement is the sum of thermal and operational demands.
| Condition | Cause | Effect on Tank Pressure | Valve Action |
|---|---|---|---|
| Outbreathing | Tank filling (pumping in), thermal expansion (heating) | Pressure increases | Vents vapor out |
| Inbreathing | Tank emptying (pumping out), thermal contraction (cooling) | Pressure decreases (vacuum) | Draws air in |
Step-by-Step Breather Valve Calculation Based on API 2000
The API 2000 standard provides a trusted, systematic method for performing a breather valve calculation for atmospheric and low-pressure storage tanks.
The process involves gathering tank and operational data, using API tables for thermal venting, calculating flow rates from pumping, summing the requirements for pressure and vacuum, and finally, selecting a valve that exceeds these calculated rates.
Following these steps ensures your chosen valve is sized correctly for safe and reliable tank protection.
Step 1: Gather Essential Data
Before you can begin any calculation, you need to collect key information about your tank and its operation. Any errors in this initial data will lead to an incorrect final sizing.
- Tank Data: Total capacity (e.g., in barrels or m³), dimensions, and design pressure/vacuum ratings.
- Operational Data: Maximum pumping rates for both filling (pumping in) and emptying (pumping out).
- Product Data: The type of liquid stored, its flash point, and its vapor pressure at operating temperatures.
- Environmental Data: Geographic location to determine likely maximum and minimum ambient temperatures.
Step 2: Determine Thermal Venting Requirements
API 2000 greatly simplifies the calculation for thermal venting. The standard provides tables that list the required flow rates based on tank capacity. For example, Table 5 in the 7th edition of API 2000 gives thermal inbreathing and outbreathing requirements for tanks up to 285,000 m³. You simply find your tank’s capacity in the table to get the required thermal venting flow rate in SCFH or Nm³/h.
Step 3: Calculate Pumping (Operational) Venting Requirements
This step calculates the venting needed due to filling and emptying the tank.
- For Outbreathing (Filling): The venting rate is based on the maximum filling rate. You must convert the liquid volume rate (e.g., m³/hr) to an equivalent vapor volume rate (Nm³/h). For example, 1 m³ of liquid can displace 1 Nm³ of vapor. The formula is straightforward: Pumping Outbreathing Rate (Nm³/h) = Max Filling Rate (m³/hr).
- For Inbreathing (Emptying): Similarly, the inbreathing rate is equal to the maximum emptying rate. As liquid is removed, an equal volume of air must enter. Pumping Inbreathing Rate (Nm³/h) = Max Emptying Rate (m³/hr).
Step 4: Sum the Total Venting Requirements
Now, you combine the thermal and operational requirements to find the total flow rate the breather valve must handle for both pressure and vacuum conditions.
- Total Outbreathing Required = Thermal Outbreathing + Pumping Outbreathing
- Total Inbreathing Required = Thermal Inbreathing + Pumping Inbreathing
You will now have two values: one for the maximum pressure relief flow and one for the maximum vacuum relief flow.
Step 5: Select the Correct Breather Valve
With your calculated flow rates, you can now select a breather valve. Review the manufacturer’s product data sheets and flow curves. You must choose a valve where the certified flow capacity at your desired set pressure (and set vacuum) is greater than or equal to your calculated total requirement. Always use the manufacturer’s certified flow curves for the final selection, as these provide the most accurate performance data.

Frequently Asked Questions (FAQ)
Q1: What is the main purpose of a breather valve calculation?
A: The main purpose of a breather valve calculation is to determine the correct size of a pressure vacuum relief valve. This ensures the valve has enough flow capacity to protect a storage tank from damage caused by overpressure or excessive vacuum during operation.
Q2: Why is the API 2000 standard important for this calculation?
A: API 2000 is the leading industry standard for venting atmospheric and low-pressure storage tanks. It provides a reliable, tested methodology and data tables for calculating venting requirements, which simplifies the process and ensures a high level of safety and consistency.
Q3: Do I need to perform the breather valve calculation for both pressure and vacuum?
A: Yes, you must perform the calculation for both conditions separately. A tank can be exposed to both overpressure (outbreathing) and vacuum (inbreathing) events. The required flow rates for each can be different, so both must be calculated to select a valve that protects against both scenarios.
Q4: What happens if my breather valve calculation is wrong?
A: An incorrect calculation can lead to an undersized or oversized valve. An undersized valve may not provide enough flow, risking tank rupture or collapse. An oversized valve can be unnecessarily expensive and may lead to “chattering” or instability, causing premature wear and tear.
Q5: Is thermal venting or pumping venting more important in the calculation?
A: Both are equally important, and the dominant factor depends on the application. For a tank with a high turnover rate (frequent filling and emptying), pumping venting will likely be the larger component. For a static storage tank, thermal venting will be the primary consideration. The total requirement is the sum of both.
Q6: Can I use the same breather valve for different chemicals?
A: Not necessarily. The breather valve calculation itself is based on flow rates, but material selection is critical. The valve’s materials must be compatible with the stored chemical to prevent corrosion and ensure reliable operation. Always verify material compatibility for your specific medium.
Final Thought
An accurate breather valve calculation is not optional—it is a cornerstone of tank farm safety and operational reliability. Using the API 2000 standard as your guide ensures your calculations are robust and your assets are protected.
At BCST, we provide high-quality breather valves and the expertise to help you with your selection process. Contact us today to ensure your tanks are equipped with the right protection.